IQ 100 Series ((130/140/150) MeterProgramming the IQ 100 Series Meter Using SoftwareUser and Installation Manual IM02601003E - July 2010 www.eaton.com 55Programming the IQ 100 Series Meter Using SoftwareOverviewThe IQ 100 Series meter can be configured using either the meter Face Buttons (Menu, Enter, Downand Right) or Eaton Meter Configuration Software. To connect to the meter for software configuration,use the RS485 port, if equipped, on the back panel of the meter.The IQ 100 Series Transducer must be configured with the Eaton Meter Configuration Software, usingthe RS485 port, since it does not have a front panel.This chapter contains instructions for programming the meter and Transducer using software.Connecting to the IQ 100 Series Meter/Transducer1. Open Eaton Meter Configuration Software.2. Click the Connect icon on the Title bar orConnection>Quick Connect.3. If you are connecting to the meter through your PC:a. Make sure the Serial Port radio button is selected.b. Enter Device Address (1-249).c. Select Baud Rate from the pull-down menu.d. Select the port you are using from the pull-down menu. TheAvailable Ports/All Ports radio buttons determine which portselections the menu displays.e. Select Modbus RTU from the Protocol pull-down menu.f. Select Flow Control: None or Hardware.g. Select Echo Mode: No Echo or Static Echo.If you are connecting to the meter through the Power Xpert® Gateway:a. Make sure the Network radio button is selected.b. Enter Device Address (1-247).c. Enter the Gateway’s IP Address.d. Enter Network Port.e. Protocol defaults to Modbus TCP.4. Click the Connect button. You will see the Device Statusscreen, shown below on the right.NOTE for IQ 100 Series Transducer:When the Transducer is powered up, for 10seconds you can connect to the meter using theFactory Initial Default Settings (even if the DeviceProfile has been changed). After 10 seconds,the Device Profile reverts to the actual DeviceProfile in use.Factory Initial Default SettingsBaud Rate: 9600Port: COM1Protocol: Modbus RTU