IQ 100 Series (130/140/150) Meter Appendix B: Modbus MapDescription1 Format Range6Units orResolution Comments#Regread-only0000 - 0007 1 - 8 Reserved none 80008 - 000F 9 - 16 Meter Serial Number ASCII 16 char none 80010 - 0010 17 - 17 Meter Type UINT16 bit-mapped -------t -------- t = transducer model (1=yes, 0=no) 10011 - 0012 18 - 19 Firmware Version ASCII 4 char none 20013 - 0013 20 - 20 Map Version UINT16 0 to 65535 none 10014 - 0014 21 - 21 Meter Configuration UINT16 bit-mapped -------- --ffffffffffff = calibration frequency (50 or 60)10015 - 0015 22 - 22 ASIC Version UINT16 0-65535 none 10016 - 0026 23 - 39 Reserved 170027 - 002E 40 - 47 Meter Name ASCII 16 char none 8Block Size: 47read-only0383 - 0384 900 - 901 Watts, 3-Ph total FLOAT -9999 M to +9999 M watts 20385 - 0386 902 - 903 VARs, 3-Ph total FLOAT -9999 M to +9999 M VARs 20387 - 0388 904 - 905 VAs, 3-Ph total FLOAT -9999 M to +9999 M VAs 2Block Size: 6read-only03E7 - 03E8 1000 - 1001 Volts A-N FLOAT 0 to 9999 M volts 203E9 - 03EA 1002 - 1003 Volts B-N FLOAT 0 to 9999 M volts 203EB - 03EC 1004 - 1005 Volts C-N FLOAT 0 to 9999 M volts 203ED - 03EE 1006 - 1007 Volts A-B FLOAT 0 to 9999 M volts 203EF - 03F0 1008 - 1009 Volts B-C FLOAT 0 to 9999 M volts 203F1 - 03F2 1010 - 1011 Volts C-A FLOAT 0 to 9999 M volts 203F3 - 03F4 1012 - 1013 Amps A FLOAT 0 to 9999 M amps 203F5 - 03F6 1014 - 1015 Amps B FLOAT 0 to 9999 M amps 203F7 - 03F8 1016 - 1017 Amps C FLOAT 0 to 9999 M amps 203F9 - 03FA 1018 - 1019 Watts, 3-Ph total FLOAT -9999 M to +9999 M watts 203FB - 03FC 1020 - 1021 VARs, 3-Ph total FLOAT -9999 M to +9999 M VARs 203FD - 03FE 1022 - 1023 VAs, 3-Ph total FLOAT -9999 M to +9999 M VAs 203FF - 0400 1024 - 1025 Power Factor, 3-Ph total FLOAT -1.00 to +1.00 none 20401 - 0402 1026 - 1027 Frequency FLOAT 0 to 65.00 Hz 20403 - 0404 1028 - 1029 Neutral Current FLOAT 0 to 9999 M amps 2Block Size: 30Primary Readings Block, 6 cycles (IEEE Floating PointModbus AddressFixed Data SectionHex DecimalIdentification BlockMeter Data Section 2Primary Readings Block, 60 cycles (IEEE Floating Point)User and Installation Manual IM02601003E - December 2009 MM-1