Eaton Corporation Page 54 Ver 1.1F) For the AC cables, the terminal connectors are recommended to beused with AC cables in order to ensure the quality of conductingbetween AC cables and AC terminal is good as shown in figure 7.2.2.3.Figure 7.2.2.3: Terminal connectors are required for AC CablesF) Next, it is to confirm the selected grid system that had been applied withthe PV inverter. And then following information of the configuration labelfor the AC cable within the wiring box in order to connect all the ACcables into correct position for the operation.Figure 7.2.2.6 indicated the AC cables connection when a 208V gridsystem applied with the PV inverter. L-phase cable connected to position(1) pole and Neutral cable connected to position (2) pole and groundcable connect to the ground symbol pole. On the other hand, pleaseensure the setting of the AC dip switch had been set correctly with theapplied grid system.Figure 7.2.2.4: Connect the AC Cables to Correct PositionG) Tighten the screws for the AC cables by the required torque as listed inthe Section D table, above. And then turn on the circuit breaker from theutility panel or switchboard in order used then multi-meter to measureand confirm the AC voltage of PV system is connected in a propersetting.