UPS OPERATING INSTRUCTIONSEATON Power Xpert 9395 UPS (1000–1100 kVA) Installation and Operation Manual 164201764 Rev 3 www.eaton.com/powerquality7-187.3.11 Start Energy Saver High Alert Mode from the BypassCommand MenuTo start High Alert mode:NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton CustomerService Engineer.NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Advanced PowerManagement is enabled, Energy Saver commands will not be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the BYPASS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The BypassControl Command screen is displayed.4. On the Bypass Control Command screen, select START HIGH ALERT.5. Press the SELECT pushbutton on the Bypass Command menu bar.If the UPS is online, the UPS starts High Alert mode with the UPMs onlinesupplying the critical load. After one hour the UPS transfers to Energy Savermode.The ONLINE status indicator is illuminated. The UPS status indicates HIGHALERT. The UPM status indicates ONLINE. The power module is on.7.3.12 Enable Advanced Power Management Mode from the BypassCommand MenuTo enable Advanced Power Management mode:NOTE The Advanced Power Management mode commands are displayed only if enabled at the factory orby an Eaton Customer Service Engineer.NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Energy Saver isenabled, Advanced Power Management commands will not be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the BYPASS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The BypassControl Command screen is displayed.4. On the Bypass Control Command screen, select ENABLE ADV POWERMANAGEMENT.5. Press the SELECT pushbutton on the Bypass Command menu bar.If the UPS is online, the UPS transfers to Advanced Power Management mode.In approximately twenty seconds the UPS calculates the required number ofUPMs needed to support the load.The ONLINE status indicator is illuminated. The UPS status indicates ONLINE +APM. The UPM status indicates ONLINE.