UPS OPERATING INSTRUCTIONSEATON Power Xpert 9395 UPS (1000–1100 kVA) Installation and Operation Manual 164201764 Rev 3 www.eaton.com/powerquality7-325. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Advanced Power Management mode. In approximatelytwenty seconds the UPS calculates the required number of UPMs needed tosupport the load.The ONLINE status indicator is illuminated. The UPS status indicates ONLINE +APM. The UPM status indicates ONLINE.7.4.6 Disable Advanced Power Management Mode from the UPSCommand MenuTo disable Advanced Power Management mode:NOTE The Advanced Power Management mode commands are displayed only if enabled at the factory orby an Eaton Customer Service Engineer.NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Energy Saver isenabled, Advanced Power Management commands will not be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select DISABLE ADV POWER MANAGEMENT.5. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Battery mode and then to Online mode in approximatelyten seconds.The ONLINE status indicator is illuminated. The UPS status indicates ONLINE. TheUPM status indicates ONLINE.7.4.7 Start Advanced Power Management High Alert Mode from the UPSCommand MenuTo start High Alert mode:NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton CustomerService Engineer.NOTE Advanced Power Management and Energy Saver modes are mutually exclusive. If Energy Saver isenabled, Advanced Power Management commands will not be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select START HIGH ALERT.