INTRODUCTIONEATON Power Xpert 9395 UPS (1000–1100 kVA) Installation and Operation Manual 164201764 Rev 3 www.eaton.com/powerquality 1-7A supplemental 48 Vdc shunt trip signal for the battery disconnect device is providedby the UPS, but is not required for normal operation.1.4 Basic System ConfigurationsThe following basic UPS system configurations are possible: Single UPS with three common battery UPMs, a common battery FI-UPM, and astandalone common battery system with a battery disconnect (four UPMconfiguration) Single UPS with three common battery UPMs, and a standalone common batterysystem with a battery disconnect (three UPM configuration) Single UPS with three separate battery UPMs, a separate battery FI-UPM, and astandalone separate battery system with a battery disconnect for each UPM (fourUPM configuration) Single UPS with three separate battery UPMs and a standalone separate batterysystem with a battery disconnect for each UPM (three UPM configuration) Distributed bypass system with two to five UPSs and a customer-suppliedtie cabinetThe UPS system configuration can be enhanced by adding optional accessories suchas a Remote Emergency Power-off (REPO) control, RMP II, or X-Slot communicationcards.The base configuration (first two digits of the configuration number) for the UPS arelisted in Table 1‐1. The configuration number can be found on the rating labelmounted on the internal safety shield panel inside the front door.Table 1‐1. Base Configuration DigitsConfiguration Base Digits1100 kVA ISBM, four UPM, Momentary Static Switch (MSS) CW1100 kVA ISBM, three UPM, MSS CY1100 kVA ISBM, four UPM, Continuous Static Switch (CSS) CH1100 kVA ISBM, three UPM, CSS CT1100 kVA IOM, four UPM CQ1.5 Using This ManualThis manual describes how to install and operate the Power Xpert 93951000–1100 kVA UPS. Read and understand the procedures described in this manualto ensure trouble-free installation and operation. In particular, be thoroughly familiarwith the REPO procedure (see paragraph 7.3.25 on page 7-28).The information in this manual is divided into sections and chapters. The system,options, and accessories being installed dictate which parts of this manual should beread. At a minimum, Chapters 1 through 4 and Chapter 7 should be examined.Read through each procedure before beginning the procedure. Perform only thoseprocedures that apply to the UPS system being installed or operated.