Serial Communication7−13EATON Powerware ® 9315 UPS (300–500 kVA) Operation Manual 164201119 Rev F www.powerware.com7.6.3 Enable/Disable Default FunctionsFrom this menu you may either enable the building alarms for general functions or specialfunctions such as On Generator, Go To Bypass, and Go To UPS. You may also customize thealarm messages from this menu. When 1 is selected from this menu, the following menu isdisplayed:Enable/Disable Default Functions1. Enable/Disable Go To Bypass2. Enable/Disable Go To UPS3. Enable/Disable On Generator4. Enable/Disable Building Alarm5. Return to Program Building Alarms MenuEnter Selection:If you select entry 1−3 from this menu, the following menu appears:Enable/Disable (Function)Enabled Building Alarm Number(s)1 4Enter E# to Enable Building Alarm Number #Enter D# to Disable Building Alarm Number #Enter for No ChangeEnter Selection:Where (Function) indicates the function the building alarm is being programmed for. Theline following the Enabled Building Alarm Number(s) label indicates which building alarmsare currently enabled for the function. (In this example, Building Alarms 1 and 4 areenabled.) A building alarm can only be programmed for one special function at a timefrom these menus. Enabling a building alarm for a special function automatically enablesthe alarm. If you disable a special function, the building alarm is also disabled.If you select entry 4 from this menu, the following menu appears:Enable/Disable Building AlarmEnabled Building Alarm Number(s)1 4Enter E# to Enable Building Alarm Number #Enter D# to Disable Building Alarm Number #Enter for No ChangeEnter Selection:The line following the Enabled Building Alarm Number(s) label indicates which buildingalarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.)