Wiring the power redundancy (PDU+1)Installing the Network Management Module – 10••••2 Installing the Network Management Module2.1 Wiring the power redundancy (PDU+1)2.1.1 Power redundancy principleInterconnect 2 Network Modules using the power redundancy port (PDU+1) with a standard Ethernet cable (not supplied).Power the 2 Network Modules with 2 different feeds so that if one feed is down, the Network Module will still be powered ON andalive, providing useful information on the power outage situation.2.1.1.1 LEDsOff — no active redundancySolid yellow — the PDU Network Module is powered by another PDU Network Modulethrough the redundancy port.Off — PDU Network Module is not connected to another PDU.Solid green — The PDU Network Module is connected to another PDU NetworkModule power redundancy port.2.1.1.2 Power redundancy connection with 2 modules2 modules:Interconnected with the PDU+1 portPowered with 2 different feedsResult with a power cut on FEED A = all the modules are powered byFEED BResult with a power cut on FEED B = all the modules are powered byFEED AYou are using an UNLICENSED copy of Scroll PDF Exporter for Confluence. Do you find Scroll PDF Exporter useful? Consider purchasing it today:https://marketplace.atlassian.com/apps/7019/scroll-pdf-exporter-for-confluence?tab=overview&hosting=datacenter