EnvironmentContextual help of the web interface – 57Press Save after modifications.4.5.1.3 Access rights per profilesAdministrator Operator ViewerEnvironment/CommissioningEnvironment/Status4.5.1.3.1 For other access rights4.5.1.4 TroubleshootingEMP communication status shows "Lost"In the Network Module, in Contextual help>>>Environment>>>Commissioning/Status , EMPs are missing in the Sensorcommissioning table.Symptom #1The connection status of the sensor is "Lost"Possible causesThe EMPs are not powered by the Network module.Action #1-1Launch again the discovery, if it is still not ok, go to Action #1-2.Action #1-21- Check the EMPs connection and cables.Refer to the sections Servicing the EMP>>>Installing the EMP>>>Cabling the first EMP to the device and Servicing theEMP>>>Installing the EMP>>>Daisy chaining 3 EMPs .2- Disconnect and reconnect the USB to RS485 cable.3- Launch the discovery, if it is still not ok, go to Action #1-3.Action #1-31- Reboot the Network module.2- Launch the discovery.Deactivated dry contacts are not displayed and replaced by this icon:For other access rights, see the Information>>>Access rights per profiles section.You are using an UNLICENSED copy of Scroll PDF Exporter for Confluence. Do you find Scroll PDF Exporter useful? Consider purchasing it today:https://marketplace.atlassian.com/apps/7019/scroll-pdf-exporter-for-confluence?tab=overview&hosting=datacenter