GE Multilin C30 Controller System 5-1155 SETTINGS 5.6 CONTROL ELEMENTS55.6.6 PID REGULATORPATH: SETTINGS CONTROL ELEMENTS PID REGULATOR PID 1(4) REGULATOR PID 1 REGULATORPID 1FUNCTION: DisabledRange: Enabled, DisabledMESSAGE PID 1 SAMPLE TIME:0.05 sRange: 0.05 to 30.00 s in steps of 0.01MESSAGE PID 1 PROCESSSIGNAL: OffRange: Off, any FlexAnalog parameterMESSAGE PID 1 SETPOINTSIGNAL: 0.00Range: -99999.99 to 99999.99 in steps of 0.01MESSAGE PID 1 TRACKING SIGNAL:OffRange: Off, any FlexAnalog parameterMESSAGE PID 1 PROPORTIONALGAIN: 1.00Range: 0.01 to 100.00 in steps of 0.01MESSAGE PID 1 SETPOINTWEIGHTING: 1.00Range: 0.01 to 1.00 in steps of 0.01MESSAGE PID 1 INTEG. TIMECONST.: 1.00 secRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PID 1 ANTIWINDUP:DisabledRange: Enabled, DisabledMESSAGE PID 1 AW TIME CONST.:1.00 secRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PID 1 DERIV. TIMECONST.: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PID 1 DERIVATIVELIMIT: 10Range: 1 to 20 in steps of 1MESSAGE PID 1 MAX:10Range: -10000 to 10000 in steps of 1MESSAGE PID 1 MIN:10Range: -10000 to 10000 in steps of 1MESSAGE PID 1 Tmin:500 msRange: 100 to 1000 ms in steps of 1MESSAGE PID 1 DEAD TIME:1.00 secRange: 1 to 20 s in steps of 1MESSAGE PID 1 BLK:OffRange: FlexLogic operandMESSAGE PID 1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE PID 1EVENTS: DisabledRange: Enabled, Disabled