GE Multilin C30 Controller System C-11APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUPCC.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.1 OVERVIEWThe C30 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.1. An ICD file is generated for the C30 by the EnerVista UR Setup software that describe the capabilities of the IED.2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-dors) for system configuration.3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settingsfile(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.The configuration process is illustrated below.Figure 0–1: IED CONFIGURATION PROCESSThe following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC61850:• BDA: Basic Data Attribute, that is not structured• DAI: Instantiated Data Attribute• DO: Data Object type or instance, depending on the context