2-14 C30 Controller System GE Multilin2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION22.2.9 TYPE TESTSC30 TYPE TESTS2.2.10 PRODUCTION TESTSTHERMALProducts go through an environmental test based upon anAccepted Quality Level (AQL) sampling process.TEST REFERENCE STANDARD TEST LEVELDielectric voltage withstand EN60255-5 2.2 kVImpulse voltage withstand EN60255-5 5 kVDamped oscillatory IEC61000-4-18 / IEC60255-22-1 2.5 kV CM, 1 kV DMElectrostatic discharge EN61000-4-2 / IEC60255-22-2 Level 3RF immunity EN61000-4-3 / IEC60255-22-3 Level 3Fast transient disturbance EN61000-4-4 / IEC60255-22-4 Class A and BSurge immunity EN61000-4-5 / IEC60255-22-5 Level 3 and 4Conducted RF immunity EN61000-4-6 / IEC60255-22-6 Level 3Power frequency immunity EN61000-4-7 / IEC60255-22-7 Class A and BVoltage interruption and ripple DC IEC60255-11 12% ripple, 200 ms interruptsRadiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class ASinusoidal vibration IEC60255-21-1 Class 1Shock and bump IEC60255-21-2 Class 1Seismic IEC60255-21-3 Class 1Power magnetic immunity IEC61000-4-8 Level 5Pulse magnetic immunity IEC61000-4-9 Level 4Damped magnetic immunity IEC61000-4-10 Level 4Voltage dip and interruption IEC61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interruptsDamped oscillatory IEC61000-4-12 2.5 kV CM, 1 kV DMConducted RF immunity, 0 to 150 kHz IEC61000-4-16 Level 4Voltage ripple IEC61000-4-17 15% rippleIngress protection IEC60529 IP40 front, IP10 backCold IEC60068-2-1 –40°C for 16 hoursHot IEC60068-2-2 85°C for 16 hoursHumidity IEC60068-2-30 6 days, variant 1Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHzRF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHzSafety UL508 e83849 NKCRSafety UL C22.2-14 e83849 NKCR7Safety UL1053 e83849 NKCR