GE Multilin C30 Controller System 6-116 ACTUAL VALUES 6.3 METERING66.3METERING 6.3.1 FLEXELEMENTSPATH: ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(8)The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.6.3.2 IEC 61580 GOOSE ANALOG VALUESPATH: ACTUAL VALUES METERING IEC 61850 GOOSE ANALOGSThe C30 Controller System is provided with optional IEC 61850 communications capability. This feature isspecified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for addi-tional details.The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are receivedvia IEC 61850 GOOSE messages sent from other devices.6.3.3 TRANSDUCER INPUTS/OUTPUTSPATH: ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xxActual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel IDand the bottom line as the value followed by the programmed units. FLEXELEMENT 1FLEXELEMENT 1OpSig: 0.000 puTable 6–1: FLEXELEMENT BASE UNITSdcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configuredunder the +IN and –IN inputs.FREQUENCY fBASE = 1 HzPHASE ANGLE BASE = 360 degrees (see the UR angle referencing convention)POWER FACTOR PF BASE = 1.00RTDs BASE = 100°CSOURCE CURRENT I BASE = maximum nominal primary RMS value of the +IN and –IN inputsSOURCE POWER PBASE = maximum value of V BASE IBASE for the +IN and –IN inputsSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs IEC 61850 GOOSE ANALOGSANALOG INPUT 10.000MESSAGE ANALOG INPUT 20.000MESSAGE ANALOG INPUT 30.000MESSAGE ANALOG INPUT 320.000 DCMA INPUT xxDCMA INPUT xx0.000 mA