GE Multilin C30 Controller System 5-1355 SETTINGS 5.7 INPUTS AND OUTPUTS55.7.13 IEC 61850 GOOSE INTEGERSPATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE UINTEGERS GOOSE UINTEGER INPUT 1(16)The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-seriesdevices. The following settings are available for each GOOSE uinteger input.• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device isoffline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integernumber.• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.The GOOSE integer input FlexInteger values are available for use in other C30 functions that use FlexInteger values. GOOSE UINTEGER INPUT 1UINTEGER 1 DEFAULT:1000Range: 0 to 429496295 in steps of 1MESSAGE UINTEGER 1 DEFAULTMODE: Default ValueRange: Default Value, Last Known