GE Multilin C30 Controller System 3-193 HARDWARE 3.2 WIRING33.2.6 TRANSDUCER INPUTS/OUTPUTSTransducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance tem-perature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and con-vert these signals into a digital format for use as required.Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configurevirtually any analog quantity used in the relay to drive the analog outputs.Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-minals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column "a"having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/output channel, the name of the channel is assigned using the module slot position and row number.Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputsrequire a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the trans-ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.Wherever a tilde “~” symbol appears, substitute with the slot position of the module.Figure 3–20: TRANSDUCER INPUT/OUTPUT MODULE WIRING3.2.7 RS232 FACEPLATE PORTA 9-pin RS232C serial port is located on the C30 faceplate for programming with a computer. All that is required to use thisinterface is a computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port isshown in the following figure for both 9-pin and 25-pin connectors.NOTE