B-60 D60 Line Distance Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BBA285 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)A286 Selector 1 Acknowledge 0 to 4294967295 --- 1 F300 0A288 Selector 1 Bit0 0 to 4294967295 --- 1 F300 0A28A Selector 1 Bit1 0 to 4294967295 --- 1 F300 0A28C Selector 1 Bit2 0 to 4294967295 --- 1 F300 0A28E Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)A28F Selector 1 Bit Acknowledge 0 to 4294967295 --- 1 F300 0A291 Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)A292 Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)A293 Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)A294 Reserved (10 items) --- --- 1 F001 0A29E ...Repeated for Selector 2Digital Counter (Read/Write Setting) (8 Modules)A300 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)A301 Digital Counter 1 Name --- --- --- F205 “Counter 1"A307 Digital Counter 1 Units --- --- --- F206 (none)A30A Digital Counter 1 Block 0 to 4294967295 --- 1 F300 0A30C Digital Counter 1 Up 0 to 4294967295 --- 1 F300 0A30E Digital Counter 1 Down 0 to 4294967295 --- 1 F300 0A311 Digital Counter 1 Preset –2147483647 to2147483647 --- 1 F004 0A313 Digital Counter 1 Compare –2147483647 to2147483647--- 1 F004 0A315 Digital Counter 1 Reset 0 to 4294967295 --- 1 F300 0A317 Digital Counter 1 Freeze/Reset 0 to 4294967295 --- 1 F300 0A319 Digital Counter 1 Freeze/Count 0 to 4294967295 --- 1 F300 0A31B Digital Counter 1 Set To Preset 0 to 4294967295 --- 1 F300 0A31D Reserved (11 items) --- --- --- F001 0A328 ...Repeated for Digital Counter 2A350 ...Repeated for Digital Counter 3A378 ...Repeated for Digital Counter 4A3A0 ...Repeated for Digital Counter 5A3C8 ...Repeated for Digital Counter 6A3F0 ...Repeated for Digital Counter 7A418 ...Repeated for Digital Counter 8Flexcurves C and D (Read/Write Setting)A600 FlexCurve C (120 items) 0 to 65535 ms 1 F011 0A680 FlexCurve D (120 items) 0 to 65535 ms 1 F011 0Non Volatile Latches (Read/Write Setting) (16 Modules)A700 Non-Volatile Latch 1 Function 0 to 1 --- 1 F102 0 (Disabled)A701 Non-Volatile Latch 1 Type 0 to 1 --- 1 F519 0 (ResetDominant)A702 Non-Volatile Latch 1 Set 0 to 4294967295 --- 1 F300 0A704 Non-Volatile Latch 1 Reset 0 to 4294967295 --- 1 F300 0A706 Non-Volatile Latch 1 Target 0 to 2 --- 1 F109 0 (Self-reset)A707 Non-Volatile Latch 1 Events 0 to 1 --- 1 F102 0 (Disabled)A708 Reserved (4 items) --- --- --- F001 0A70C ...Repeated for Non-Volatile Latch 2A718 ...Repeated for Non-Volatile Latch 3A724 ...Repeated for Non-Volatile Latch 4A730 ...Repeated for Non-Volatile Latch 5A73C ...Repeated for Non-Volatile Latch 6A748 ...Repeated for Non-Volatile Latch 7A754 ...Repeated for Non-Volatile Latch 8A760 ...Repeated for Non-Volatile Latch 9Table B–10: MODBUS MEMORY MAP (Sheet 52 of 77)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT