B-66 D60 Line Distance Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BBB228 ...Repeated for Received Analog 13B22A ...Repeated for Received Analog 14B22C ...Repeated for Received Analog 15B22E ...Repeated for Received Analog 16B230 ...Repeated for Received Analog 17B232 ...Repeated for Received Analog 18B234 ...Repeated for Received Analog 19B236 ...Repeated for Received Analog 20B238 ...Repeated for Received Analog 21B23A ...Repeated for Received Analog 22B23C ...Repeated for Received Analog 23B23E ...Repeated for Received Analog 24B240 ...Repeated for Received Analog 25B242 ...Repeated for Received Analog 26B244 ...Repeated for Received Analog 27B246 ...Repeated for Received Analog 28B248 ...Repeated for Received Analog 29B24A ...Repeated for Received Analog 30B24C ...Repeated for Received Analog 31B24E ...Repeated for Received Analog 32IEC 61850 Configurable Report Settings (Read/Write Setting)B290 IEC 61850 configurable reports dataset items (64 items) 0 to 848 --- 1 F615 0 (None)Wattmetric Ground Fault Settings (read/write grouped, 5 Modules)B300 Wattmetric ground fault 1 function 0 to 1 --- 1 F102 0 (Disabled)B301 Wattmetric ground fault 1 source 0 to 5 --- 1 F167 0 (SRC 1)B302 Wattmetric ground fault 1 voltage 0 to 1 --- 1 F234 0 (Calculated VN)B303 Wattmetric ground fault 1 overvoltage pickup 0.02 to 3.00 pu 0.01 F001 20B304 Wattmetric ground fault 1 current 0 to 1 --- 1 F235 0 (Calculated IN)B305 Wattmetric ground fault 1 overcurrent pickup 0.002 to 30.000 pu 0.001 F001 60B306 Wattmetric ground fault 1 overcurrent pickup delay 0 to 600 s 0.01 F001 20B307 Wattmetric ground fault 1 power pickup 0.001 to 1.2 pu 0.001 F001 100B308 Wattmetric ground fault 1 ECA 0 to 360 ° Lag 1 F001 0B309 Wattmetric ground fault 1 power pickup delay 0 to 600 s 0.01 F001 20B30A Wattmetric ground fault 1 curve 0 to 5 --- 1 F236 0 (Definite Time)B30B Wattmetric ground fault 1 multiplier 0.01 to 2 s 0.01 F001 100B30C Wattmetric ground fault 1 block 0 to 65535 --- 1 F300 0B30E Wattmetric ground fault 1 target 0 to 2 --- 1 F109 0 (Self-reset)B30F Wattmetric ground fault 1 events 0 to 1 --- 1 F102 0 (Disabled)B310 Wattmetric ground fault 1 reference power 0.001 to 1.2 pu 0.001 F001 500B311 Wattmetric ground fault x Reserved 0 to 1 --- 1 F001 0B312 ...Repeated for wattmetric ground fault 2B324 ...Repeated for wattmetric ground fault 3B336 ...Repeated for wattmetric ground fault 4B348 ...Repeated for wattmetric ground fault 5Wattmetric Ground Fault Actual Values (Read Only) (5 Modules)B360 Wattmetric ground fault 1 operating power 0 to 999999.999 W 0.001 F060 0B362 ...Repeated for wattmetric ground fault 2B364 ...Repeated for wattmetric ground fault 3B366 ...Repeated for wattmetric ground fault 4B368 ...Repeated for wattmetric ground fault 5IEC 61850 XSWI Configuration (Read/Write Setting) (24 Modules)B370 Flexlogic Operand for IEC 61850 XSWI.ST.Loc Status 0 to 4294967295 --- 1 F300 0IEC 61850 XSWI Configuration (Read/Write Command) (24 Modules)B372 Command to Clear XSWI OpCnt (Operation Counter) 0 to 1 --- 1 F126 0 (No)Table B–10: MODBUS MEMORY MAP (Sheet 58 of 77)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT