5-24 G30 Generator Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5Multiple LANS, with RedundancyThe topology in the following figure provides local configuration/monitoring through EnerVista software and access to thepublic network shared on LAN1, to which port 1 (P1) is connected. There is no redundancy provided on LAN1. Communica-tions to SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 isthe redundant channel. In this configuration, P3 uses the IP and MAC address of P2.Figure 5–4: MULTIPLE LANS, WITH REDUNDANCYMultiple LANS, No RedundancyThe following topology provides local configuration/monitoring through EnerVista software on LAN1, to which port 1 (P1) isconnected, access to the public network on LAN2, to which port 2 (P2) is connected and communications with SCADA onLAN3, to which port 3 (P3) is connected. There is no redundancy.Figure 5–5: MULTIPLE LANS, NO REDUNDANCYP3IP2/MAC2EnerVista SoftwareML3000Public NetworkSCADAURP1IP1/MAC1P2IP2/MAC2ML3000 ML3000Redundancy modeLAN1 LAN2 LAN2859709A4.vsdEnerVista SoftwareML3000Public NetworkSCADAURP1IP1/MAC1P2IP2/MAC2ML3000 ML3000LAN1 LAN2LAN3P3IP3/MAC3859710A2.vsd