GE Multilin G30 Generator Protection System B-41APPENDIX B B.4 MEMORY MAPPINGB7794 Thermal Protection 1 Events 0 to 1 --- 1 F102 0 (Disabled)7795 Reserved (2 items) --- --- --- F001 07797 Repeated for Thermal Protection 2Ohm Inputs (Read/Write Setting) (2 modules)77F8 Ohm Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)77F9 Ohm Inputs 1 ID --- --- --- F205 "Ohm Ip 1 "77FF Ohm Inputs 1 Reserved (9 items) 0 to 65535 --- 1 F001 07808 ...Repeated for Ohm Inputs 2Underfrequency (Read/Write Setting) (6 modules)7A80 Underfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)7A81 Underfrequency 1 Block 0 to 4294967295 --- 1 F300 07A83 Underfrequency 1 Min Current 0.1 to 1.25 pu 0.01 F001 107A84 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 59507A85 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 20007A86 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 20007A87 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)7A88 Underfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)7A89 Underfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)7A8A Underfrequency 1 Reserved (5 items) 0 to 1 --- 1 F001 07A8F ...Repeated for Underfrequency 27A9E ...Repeated for Underfrequency 37AAD ...Repeated for Underfrequency 47ABC ...Repeated for Underfrequency 57ACB ...Repeated for Underfrequency 6User Programmable Pushbuttons (Read/Write Setting) (16 modules)7B60 User Programmable Pushbutton 1 Function 0 to 2 --- 1 F137 0 (Disabled)7B61 User Programmable Pushbutton 1 Top Line --- --- --- F202 (none)7B6B User Programmable Pushbutton 1 On Text --- --- --- F202 (none)7B75 User Programmable Pushbutton 1 Off Text --- --- --- F202 (none)7B7F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 s 0.05 F001 07B80 User Programmable Pushbutton 1 Target 0 to 2 --- 1 F109 0 (Self-reset)7B81 User Programmable Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)7B82 User Programmable Pushbutton 1 LED Operand 0 to 4294967295 --- 1 F300 07B84 User Programmable Pushbutton 1 Autoreset Delay 0.2 to 600 s 0.1 F001 107B85 User Programmable Pushbutton 1 Autoreset Function 0 to 1 --- 1 F102 0 (Disabled)7B86 User Programmable Pushbutton 1 Local Lock Operand 0 to 4294967295 --- 1 F300 07B88 User Programmable Pushbutton 1 Message Priority 0 to 2 --- 1 F220 0 (Disabled)7B89 User Programmable Pushbutton 1 Remote Lock Operand 0 to 4294967295 --- 1 F300 07B8B User Programmable Pushbutton 1 Reset Operand 0 to 4294967295 --- 1 F300 07B8D User Programmable Pushbutton 1 Set Operand 0 to 4294967295 --- 1 F300 07B8F User Programmable Pushbutton 1 Hold 0 to 10 s 0.1 F001 17B90 ...Repeated for User Programmable Pushbutton 27BC0 ...Repeated for User Programmable Pushbutton 37BF0 ...Repeated for User Programmable Pushbutton 47C20 ...Repeated for User Programmable Pushbutton 57C50 ...Repeated for User Programmable Pushbutton 67C80 ...Repeated for User Programmable Pushbutton 77CB0 ...Repeated for User Programmable Pushbutton 87CE0 ...Repeated for User Programmable Pushbutton 97D10 ...Repeated for User Programmable Pushbutton 107D40 ...Repeated for User Programmable Pushbutton 117D70 ...Repeated for User Programmable Pushbutton 127DA0 ...Repeated for User Programmable Pushbutton 137DD0 ...Repeated for User Programmable Pushbutton 14Table B–10: MODBUS MEMORY MAP (Sheet 33 of 60)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT