CHAPTER 4: INTERFACES FRONT PANEL INTERFACEG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-234User customization of LED operation is of maximum benefit in installations where languages other than English are usedto communicate with operators. See the User-programmable LEDs section in chapter 5 for the settings used to programthe operation of the LEDs on these panels.Figure 4-25: LED panels 2 and 3 (index template)Default labels for LED panel 2The default labels are intended to represent the following:• GROUP 1...6 — The illuminated GROUP is the active settings group• SYNCHROCHECK NO1(4) IN-SYNCH — Voltages have satisfied the synchrocheck elementThe relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match thepre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. TheLEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained inthe next section.Figure 4-26: LED panel 2 (default labels)4.2.8 Custom LED labeling4.2.8.1 Enhanced faceplateThe following procedure requires these pre-requisites:• EnerVista UR Setup software is installed and operational• The G30 settings have been saved to a settings file• The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded fromhttp://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed• Small-bladed knifeTo create custom LED labels for the enhanced front panel display:1. Start the EnerVista UR Setup software.