CHAPTER 5: SETTINGS PRODUCT SETUPG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-795XSWI1 Pos ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-enhanced-securityDefault: sbo-with-enhanced-securityThis setting selects the control model that clients must use to successfully control the disconnect switch 1 signalsmarked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings> System Setup section later. These signals force a disconnect switch trip or close control while the operand selected bysetting XSWI1 ST.LOC OPERAND is not active."sbo" here is select-before-operate. Enhanced security means that the G30 reports to the client the disconnect switch 1position the end of the command sequence.XSWI1 Pos sboTimeoutRange: 2 to 60 s in steps of 1 sDefault: 30 sThis setting specifies the maximum time between a select and an operate command to disconnect switch 1 signalsmarked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal in order for the operand to be successful. This setting isonly relevant when XSWI1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.Disc0XSWI1 BlkOpn ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the disconnect switch 1 signal markedDiscCSWI1.BlkOpn.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. Thissignal when true blocks disconnect switch 1 trip control while the operand selected by setting XSWI1 ST.LOC OPERAND isnot active.Disc0XSWI1 BlkCls ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the disconnect switch 1 signal markedDiscCSWI1.BlkCls.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. Thissignal when true blocks disconnect switch 1 close control while the operand selected by setting XSWI1 ST.LOC OPERANDis not active.Disc0CSWI1 Pos ctlModelRange: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-enhanced-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the disconnect switch 1 signals markedDiscCSWI1.PosOpn.ctlVal and DiscCSWI1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings > SystemSetup section later. These signals force a disconnect switch trip or close control while the operand selected by settingXSWI1 ST.LOC OPERAND is not active.Disc0CSWI1 Pos sboTimeoutRange: 2 to 60 s in steps of 1 sDefault: 30 sThis setting specifies the maximum time between a select and an operate command to disconnect switch 1 viaBkrCSWI1.Pos in order for the operand to be successful. This setting is only relevant when CSWI1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.Disc0CSWI1 Pos operTimeoutRange: 0.000 to 65.535 s in steps of 0.001sDefault: 5.000 sThis setting specifies the maximum time between an operate command to disconnect switch 1 via BkrCSWI1.Pos untilBkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached inthe set time.