CHAPTER 5: SETTINGS PRODUCT SETUPG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-10755.3.12 Control pushbuttonsSETTINGS PRODUCT SETUP CONTROL PUSHBUTTONS CONTROL PUSHBUTTON 1(7)There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced frontpanels. These are user-programmable and can be used for various applications such as performing an LED test, switchingsetting groups, and invoking and scrolling though user-programmable displays.The location of the control pushbuttons are shown in the following figures.Figure 5-43: Control pushbuttons (enhanced faceplate)An additional four control pushbuttons are included on the standard faceplate when the G30 is ordered with the 12 user-programmable pushbutton option.Figure 5-44: Control pushbuttons (standard faceplate)Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.Each control pushbutton asserts its own FlexLogic operand. Each operand need to be configured appropriately to performthe required function. Each operand remains asserted as long as the pushbutton is pressed and resets when thepushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation is recognizedby various features that can use control pushbuttons as inputs. CONTROL PUSHBUTTON 1 CONTROL PUSHBUTTN 1 IDCTRL PB 1Range: up to 20 alphanumeric characters CONTROL PUSHBUTTON 1FUNCTION: DisabledRange: Disabled, Enabled CONTROL PUSHBUTTON 1EVENTS: DisabledRange: Disabled, Enabled