CHAPTER 5: SETTINGS SYSTEM SETUPG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-14155.5.5 BreakersSETTINGS SYSTEM SETUP BREAKERS BREAKER 1(2)A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Information toprogram the settings is covered here. These features are provided for two or more breakers; a user can use only thoseportions of the design relevant to a single breaker, which must be breaker 1.The number of breaker control elements depends on the number of CT/VT modules specified with the G30. The followingsettings are available for each breaker control element. BREAKER 1 BREAKER 1FUNCTION: DisabledRange: Disabled, Enabled BREAKER1 PUSH BUTTONCONTROL: DisabledRange: Disabled, Enabled BREAKER 1 NAME:Bkr 1Range: up to six alphanumeric characters BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-Pole BREAKER 1 OPEN:OffRange: FlexLogic operand BREAKER 1 BLK OPEN:OffRange: FlexLogic operand BREAKER 1 CLOSE:OffRange: FlexLogic operand BREAKER 1 BLK CLOSE:OffRange: FlexLogic operand BREAKER1 ΦA/3P CLSD:OffRange: FlexLogic operand BREAKER1 ΦA/3P OPND:OffRange: FlexLogic operand BREAKER 1 ΦB CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦB OPENED:OffRange: FlexLogic operand BREAKER 1 ΦC CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦC OPENED:OffRange: FlexLogic operand BREAKER 1 TOPERATE:70 msRange: 0 to 65535 s in steps of 1 BREAKER 1 EXT ALARM:OffRange: FlexLogic operand BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 BREAKER 1 OUT OF SV:OffRange: FlexLogic operand BREAKER 1 EVENTS:DisabledRange: Disabled, Enabled