CHAPTER 6: ACTUAL VALUES STATUSG30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-96The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/outputring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the lastten messages. There are two return times for dual-channel communications modules.The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do notmake the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count thedirect output messages that have been received but fail the CRC check. High values for either of these counts can indicateon a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAILCOUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.6.3.16 Direct devices statusACTUAL VALUES STATUS DIRECT DEVICES STATUSThese actual values represent the state of direct devices 1 through 16.6.3.17 EGD protocol status6.3.17.1 Fast exchangeACTUAL VALUES STATUS EGD PROTOCOL STATUS PRODUCER STATUS FAST EXCHANGE 1These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet sizefor the fast EGD exchange display. CRC FAIL COUNTCH1: 0 AVERAGE MSG RETURNTIME CH2: 0 ms UNRETURNED MSGCOUNT CH2: 0 CRC FAIL COUNTCH2: 0 DIRECT INPUT 1:On DIRECT INPUT 32:On DIRECT DEVICES STATUS DIRECT DEVICE 1STATUS: OfflineRange: Offline, Online DIRECT DEVICE 16STATUS: OfflineRange: Offline, Online FAST EXCHANGE 1 FAST EXCHANGE 1SIGNATURE: 0 FAST EXCHANGE 1DATA LENGTH: 0