GE Multilin L30 Line Current Differential System 5-1535 SETTINGS 5.5 FLEXLOGIC58. The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations willthen only be evaluated up to the first "END" operator.The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, andthe "INSERT" and "DELETE" commands can be used to modify equations.5.5.5 FLEXLOGIC EQUATION EDITORPATH: SETTINGS FLEXLOGIC FLEXLOGIC EQUATION EDITORThere are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Elementis selected as a FlexLogic entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when editingFlexLogic equations from the keypad to quickly scan through the major parameter types.5.5.6 FLEXLOGIC TIMERSPATH: SETTINGS FLEXLOGIC FLEXLOGIC TIMERS FLEXLOGIC TIMER 1(32)There are 32 identical FlexLogic timers available. These timers can be used as operators for FlexLogic equations.• TIMER 1 TYPE: This setting is used to select the time measuring unit.• TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".• TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0". FLEXLOGIC EQUATION EDITORFLEXLOGIC ENTRY 1:ENDRange: FlexLogic operandsMESSAGE FLEXLOGIC ENTRY 2:ENDRange: FlexLogic operands↓MESSAGE FLEXLOGIC ENTRY 512:ENDRange: FlexLogic operands FLEXLOGIC TIMER 1TIMER 1TYPE: millisecondRange: millisecond, second, minuteMESSAGE TIMER 1 PICKUPDELAY: 0Range: 0 to 60000 in steps of 1MESSAGE TIMER 1 DROPOUTDELAY: 0Range: 0 to 60000 in steps of 1