F-8 L30 Line Current Differential System GE MultilinF.2 DNP POINT LISTS APPENDIX FFF.2DNP POINT LISTS F.2.1 BINARY INPUT POINTSThe DNP binary input data points are configured through the PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINTLISTS BINARY INPUT / MSP POINTS menu. See the Communications section of Chapter 5 for details. When a freeze func-tion is performed on a binary counter point, the frozen value is available in the corresponding frozen counter point.BINARY INPUT POINTSStatic (Steady-State) Object Number: 1Change Event Object Number: 2Request Function Codes supported: 1 (read), 22 (assign class)Static Variation reported when variation 0 requested: 2 (Binary Input with status), ConfigurableChange Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), ConfigurableChange Event Scan Rate: 8 times per power system cycleChange Event Buffer Size: 500Default Class for All Points: 1