5-46 L30 Line Current Differential System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5Figure 5–6: CONTROL PUSHBUTTON LOGIC5.2.13 USER-PROGRAMMABLE PUSHBUTTONSPATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1(16) USER PUSHBUTTON 1PUSHBUTTON 1FUNCTION: DisabledRange: Self-Reset, Latched, DisabledMESSAGE PUSHBTN 1 ID TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 ON TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 OFF TEXT: Range: Up to 20 alphanumeric charactersMESSAGE PUSHBTN 1 HOLD:0.0 sRange: 0.0 to 10.0 s in steps of 0.1MESSAGE PUSHBTN 1 SET:OffRange: FlexLogic™ operandMESSAGE PUSHBTN 1 RESET:OffRange: FlexLogic™ operandMESSAGE PUSHBTN 1 AUTORST:DisabledRange: Disabled, EnabledMESSAGE PUSHBTN 1 AUTORSTDELAY: 1.0 sRange: 0.2 to 600.0 s in steps of 0.1MESSAGE PUSHBTN 1 REMOTE:OffRange: FlexLogic™ operandMESSAGE PUSHBTN 1 LOCAL:OffRange: FlexLogic™ operandMESSAGE PUSHBTN 1 DROP-OUTTIME: 0.00 sRange: 0 to 60.00 s in steps of 0.05MESSAGE PUSHBTN 1 LED CTL:OffRange: FlexLogic™ operandMESSAGE PUSHBTN 1 MESSAGE:DisabledRange: Disabled, Normal, High PriorityMESSAGE PUSHBUTTON 1EVENTS: DisabledRange: Disabled, Enabled842010A2.CDRCONTROL PUSHBUTTON1 FUNCTION:SYSTEM SETUP/BREAKERS/BREAKER 1/BREAKER 1 PUSHBUTTON:CONTROLSYSTEM SETUP/BREAKERS/BREAKER 2/BREAKER 2 PUSHBUTTON:CONTROLSETTINGSETTINGSTIMER FLEXLOGIC OPERANDEnabled=1Enabled=1When applicableEnabled=1RUNOFFONAND100 msec0 CONTROL PUSHBTN 1 ON{