GE Multilin L30 Line Current Differential System 5-895 SETTINGS 5.4 SYSTEM SETUP5Figure 5–33: CURRENT TRIGGER SCHEME LOGICj) POWER TRIGGERINGPATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 POWER TRIGGERThis element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. Interms of signaling its operation the element does not differentiate between the three types of power. The trigger responds tothe single-phase and three-phase power signals of the phasor measurement unit (PMU) source.• PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. Forsingle-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phasepower. The comparator applies a 3% hysteresis.• PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of thesource. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-gle-phase power. The comparator applies a 3% hysteresis. PMU 1 POWER TRIGGERPMU 1 POWER TRIGGERFUNCTION: DisabledRange: Enabled, DisabledMESSAGE PMU 1 POWER TRIGGERACTIVE: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001MESSAGE PMU 1 POWER TRIGGERREACTIVE: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001MESSAGE PMU 1 POWER TRIGGERAPPARENT: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001MESSAGE PMU 1 POWER TRIGGERPKP TIME: 0.10 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PMU 1 POWER TRIGGERDPO TIME: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PMU 1 PWR TRIG BLK:OffRange: FlexLogic™ operandMESSAGE PMU 1 POWER TRIGGERTARGET: Self-ResetRange: Self-Reset, Latched, DisabledMESSAGE PMU 1 POWER TRIGGEREVENTS: DisabledRange: Enabled, DisabledSETTINGSPMU 1 CURR TRIGGERFUNCTION:Enabled = 1PMU 1 CURR TRIG BLK:Off = 0SETTINGSPMU 1 SIGNALSOURCE:ANDSETTINGSPMU 1 CURR TRIGGER PICKUP:RUNSETTINGSPMU 1 CURR TRIGGER PKP TIME:PMU 1 CURR TRIGGER DPO TIME:tPKPtDPOFLEXLOGIC OPERANDPMU 1 CURR TRIGGERFLEXLOGIC OPERANDSPMU 1 FREQ TRIGGERPMU 1 VOLT TRIGGERPMU 1 POWER TRIGGERPMU 1 ROCOF TRIGGERSETTINGPMU 1 USER TRIGGER:Off = 0OR FLEXLOGIC OPERANDPMU 1 TRIGGEREDto STAT bits ofthe data frameIA I > PICKUPI > PICKUPI > PICKUPORIBIC 847000A1.CDR