C-8 L30 Line Current Differential System GE MultilinC.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE APPENDIX CCItems programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping,blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmis-sion of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission.Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if anychanges have been made. If any changes in the data items are detected, these changes will be transmitted through aGOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if nochanges in the data items are detected.The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-sages due to an oscillation being created that is triggering a message.The L30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can becaused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed stationcomponents. If erroneously oscillation is detected, the L30 will stop sending GOOSE messages from the dataset for a min-imum period of one second. Should the oscillation persist after the one second time-out period, the L30 will continue toblock transmission of the dataset. The L30 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-sage on the front panel display, where XXX denotes the data item detected as oscillating.The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-seriesIEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE datatransfer between UR-series IEDs.IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve thesuccessful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exactmatch in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration ispossible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup-software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer tothe IEC 61850 IED configuration section later in this appendix).The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. Thegeneral steps required for transmission configuration are:1. Configure the transmission dataset.2. Configure the GOOSE service settings.3. Configure the data.The general steps required for reception configuration are:1. Configure the reception dataset.2. Configure the GOOSE service settings.3. Configure the data.This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point statusvalue, its associated quality flags, and a floating point analog value.The following procedure illustrates the transmission configuration.1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØIEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLEGOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.The transmission dataset now contains a set of quality flags and a single point status Boolean value. The receptiondataset on the receiving device must exactly match this structure.2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATIONÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-RABLE GOOSE 1 settings menu: