GE Multilin L30 Line Current Differential System B-43APPENDIX B B.4 MEMORY MAPPINGB7F40 ...Repeated for Auxiliary Overvoltage 27F50 ...Repeated for Auxiliary Overvoltage 3Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 7007F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 1007F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 1007F66 Auxiliary Undervoltage 1 Block 0 to 65535 --- 1 F300 07F67 Auxiliary Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)7F68 Auxiliary Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)7F69 Reserved (7 items) 0 to 65535 --- 1 F001 07F70 ...Repeated for Auxiliary Undervoltage 27F80 ...Repeated for Auxiliary Undervoltage 3Frequency (Read Only)8000 Tracking Frequency 2 to 90 Hz 0.01 F001 0Temp Monitor Actual Values (Read Only Non-Volatile)81C0 Reserved Register T1 -55 to 125 C 1 F002 -5581C1 Reserved Register T2 -55 to 125 C 1 F002 12581C2 Reserved Register T3 -2147483647 to2147483647--- 1 F004 081C4 Reserved Register T4 0 to 4294967295 --- 1 F003 081C6 Reserved Register T5 0 to 4294967295 --- 1 F003 081C8 Reserved Register T6 0 to 4294967295 --- 1 F003 081CA Reserved Register T7 0 to 4294967295 --- 1 F003 081CC Reserved Register T8 0 to 4294967295 --- 1 F003 0Breaker Failure (Read/Write Grouped Setting) (2 modules)8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)8605 Breaker Failure 1 Three Pole Initiate 0 to 65535 --- 1 F300 08606 Breaker Failure 1 Block 0 to 65535 --- 1 F300 08607 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 pu 0.001 F001 10508608 Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 pu 0.001 F001 10508609 Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)860A Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0860B Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)860C Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0860D Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)860E Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 0860F Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 65535 --- 1 F300 08610 Breaker Failure 1 Breaker Status 2 Phase A/3P 0 to 65535 --- 1 F300 08611 Breaker Failure 1 Breaker Test On 0 to 65535 --- 1 F300 08612 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 10508613 Breaker Failure 1 Neutral Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 10508614 Breaker Failure 1 Phase Amp Loset Pickup 0.001 to 30 pu 0.001 F001 10508615 Breaker Failure 1 Neutral Amp Loset Pickup 0.001 to 30 pu 0.001 F001 10508616 Breaker Failure 1 Loset Time 0 to 65.535 s 0.001 F001 08617 Breaker Failure 1 Trip Dropout Delay 0 to 65.535 s 0.001 F001 08618 Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)8619 Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)Table B–10: MODBUS MEMORY MAP (Sheet 35 of 57)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT