GE Multilin L60 Line Phase Comparison Relay 5-575 SETTINGS 5.3 SYSTEM SETUP55.3.4 BREAKERSPATH: SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2)A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-tion concerning programming of the associated settings is covered here. These features are provided for two breakers; auser may use only those portions of the design relevant to a single breaker, which must be breaker 1.• BREAKER 1(2) FUNCTION: Set to "Enable" to allow the operation of any breaker control feature.• BREAKER1(2) PUSH BUTTON CONTROL: Set to "Enable" to allow faceplate push button operations.• BREAKER 1(2) NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used inflash messages related to breaker 1.• BREAKER 1(2) MODE: Selects "3-pole" mode, where all breaker poles are operated simultaneously, or "1-pole" modewhere all breaker poles are operated either independently or simultaneously.• BREAKER 1(2) OPEN: Selects an operand that creates a programmable signal to operate an output relay to openBreaker No. 1.• BREAKER 1(2) CLOSE: Selects an operand that creates a programmable signal to operate an output relay to closeBreaker No. 1.• BREAKER 1(2) ΦA/3-POLE: Selects an operand, usually a contact input connected to a breaker auxiliary positiontracking mechanism. This input can be either a 52/a or 52/b contact, or a combination the 52/a and 52/b contacts, thatmust be programmed to create a logic 0 when the breaker is open. If BREAKER 1 MODE is selected as "3-Pole", this set-ting selects a single input as the operand used to track the breaker open or closed position. If the mode is selected as BREAKER 1BREAKER 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE BREAKER1 PUSH BUTTONCONTROL: DisabledRange: Disabled, EnabledMESSAGE BREAKER 1 NAME:Bkr 1Range: up to 6 alphanumeric charactersMESSAGE BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-PoleMESSAGE BREAKER 1 OPEN:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 CLOSE:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φA/3-POLE:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φB:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φC:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 EXT ALARM:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 1 000 000.000 s in steps of 0.001MESSAGE MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 1 000 000.000 s in steps of 0.001MESSAGE BREAKER 1 OUT OF SV:OffRange: FlexLogic™ operand