GE Multilin L60 Line Phase Comparison Relay 2-192 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS22.2.11 TYPE TESTSElectrical fast transient: ANSI/IEEE C37.90.1IEC 61000-4-4IEC 60255-22-4Oscillatory transient: ANSI/IEEE C37.90.1IEC 61000-4-12Insulation resistance: IEC 60255-5Dielectric strength: IEC 60255-6ANSI/IEEE C37.90Electrostatic discharge: EN 61000-4-2Surge immunity: EN 61000-4-5RFI susceptibility: ANSI/IEEE C37.90.2IEC 61000-4-3IEC 60255-22-3Ontario Hydro C-5047-77Conducted RFI: IEC 61000-4-6Voltage dips/interruptions/variations:IEC 61000-4-11IEC 60255-11Power frequency magnetic field immunity:IEC 61000-4-8Pulse magnetic field immunity: IEC 61000-4-9Vibration test (sinusoidal): IEC 60255-21-1Shock and bump: IEC 60255-21-2Seismic: IEC 60255-21-3IEEE C37.98Cold: IEC 60028-2-1, 16 h at –40°CDry heat: IEC 60028-2-2, 16 h at 85°CType test report available upon request.2.2.12 PRODUCTION TESTSTHERMALProducts go through an environmental test based upon anAccepted Quality Level (AQL) sampling process.2.2.13 APPROVALSAPPROVALSUL Listed for the USA and CanadaCE:LVD 73/23/EEC: IEC 1010-1EMC 81/336/EEC: EN 50081-2, EN 50082-22.2.14 MAINTENANCEMOUNTINGAttach mounting brackets using 20 inch-pounds (±2 inch-pounds)of torque.CLEANINGNormally, cleaning is not required; but for situations where dusthas accumulated on the faceplate display, a dry cloth can be used.Units that are stored in a de-energized state should bepowered up once per year, for one hour continuously, toavoid deterioration of electrolytic capacitors.NOTENOTE