GE Multilin L90 Line Differential Relay 5-715 SETTINGS 5.4 FLEXLOGICô5Figure 5ñ32: FLEXELEMENTô DIRECTION, PICKUP, AND HYSTERESISIn conjunction with the FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac-teristics as shown in the figure below.Figure 5ñ33: FLEXELEMENTô INPUT MODE SETTINGFlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = OverPICKUPHYSTERESIS = % of PICKUPFlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = UnderPICKUPHYSTERESIS = % of PICKUP842705A1.CDR842706A2.CDRFlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = Over;FLEXELEMENT INPUTMODE = Signed;FlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = Over;FLEXELEMENT INPUTMODE = Absolute;FlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = Under;FLEXELEMENT INPUTMODE = Signed;FlexElement 1 OpSigFLEXELEMENT 1 PKPFLEXELEMENTDIRECTION = Under;FLEXELEMENT INPUTMODE = Absolute;