1-10 B30 Bus Differential System GE Multilin1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED1 3. Click the Quick Connect button to open the Quick Connect dialog box.4. Select the Serial interface and the correct COM Port, then click Connect.5. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directlyfrom the B30 device.Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-tions to the B30. This ensures that configuration of the EnerVista UR Setup software matches the B30 model number.B) USING QUICK CONNECT VIA THE REAR ETHERNET PORTSTo use the Quick Connect feature to access the B30 from a computer through Ethernet, first assign an IP address to therelay from the front panel keyboard.1. Press the MENU key until the SETTINGS menu is displayed.2. Navigate to the SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS setting.3. Enter an IP address of “1.1.1.1” and select the ENTER key to save the value.4. In the same menu, select the SUBNET IP MASK setting.5. Enter a subnet IP address of “255.0.0.0” and press the ENTER key to save the value.Next, use an Ethernet cross-over cable to connect the computer to the rear Ethernet port. The pinout for an Ethernet cross-over cable is shown below.FIGURE 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUTNow, assign the computer an IP address compatible with the relay’s IP address.842799A1.CDREND 1 END 2Pin Wire color Diagram Pin Wire color Diagram1 White/orange 1 White/green2 Orange 2 Green3 White/green 3 White/orange4 Blue 4 Blue5 White/blue 5 White/blue6 Green 6 Orange7 White/brown 7 White/brown8 Brown 8 Brown12 3 4 5 678