5: SPECIAL FUNCTIONS5-2 « FC4A MICRO SMART USER ’S MANUAL »Stop Input and Reset InputAs described on page 4-3, the MicroSmart can be started and stopped using a stop input or reset input, which can be desig-nated from the Function Area Settings menu. When the designated stop or reset input is turned on, the MicroSmart stopsoperation. For the system statuses in the stop and reset modes, see page 4-4.Since these settings relate to the user program, the user program must be downloaded to the MicroSmart after changingany of these settings.Programming WindLDR1. From the WindLDR menu bar, select Configure > Function Area Settings. The Function Area Settings dialog boxappears.2. Select the Run/Stop tab.Stop Input: Click the check box on the left of Use Stop Input and type a desired input number available on the CPUmodule in the Stop Input field.Reset Input: Click the check box on the left of Use Reset Input and type a desired reset number available on the CPUmodule in the Reset Input field.Default: No stop and reset inputs are designated.3. Click the OK button.This example designatesinput I0 as a stop input andinput I1 as a reset input.