24: ANALOG I/O CONTROL« FC4A MICRO SMART USER ’S MANUAL » 24-11Analog Input ParametersAnalog input parameters include the analog input signal type, analog input data type, analog input minimum and maxi-mum values, filter value, thermistor parameter, analog input data, and analog input operating status. This section describesthese parameters in detail.Analog Input Signal TypeA total of 11 analog input signal types are available, depending on the analog I/O or analog input module. Select an analoginput signal type for each analog input channel. When a channel is not used, select the default value or Not used for thechannel.Analog Input Data TypeA total of five analog input data types are available, depending on the analog I/O or analog input module. Select an analoginput data type for each analog input channel.Binary DataWhen Binary data is selected as an analog input data type, the analog input is linearly converted into digital data in therange described in the table below.Parameter FC4A-L03A1FC4A-L03AP1FC4A-J2A1FC4A-J4CN1FC4A-J8C1FC4A-J8AT10 Voltage input (0 to 10V DC) X — X X X —1 Current input (4 to 20 mA DC) X — X X X —2 Type K thermocouple — X — X — —3 Type J thermocouple — X — X — —4 Type T thermocouple — X — X — —5 Pt 100 resistance thermometer — X — X — —6 Pt 1000 resistance thermometer — — — X — —7 Ni 100 resistance thermometer — — — X — —8 Ni 1000 resistance thermometer — — — X — —9 NTC type thermistor — — — — — X10 PTC type thermistor — — — — — X255 Not used — — — X X XParameter FC4A-L03A1FC4A-L03AP1FC4A-J2A1FC4A-J4CN1FC4A-J8C1FC4A-J8AT10 Binary data X X X X X X1 Optional range X X X X X X2 Celsius — X — X — NTC only3 Fahrenheit — X — X — NTC only4 Resistance — — — — — XType No.FC4A-L03A1FC4A-L03AP1FC4A-J2A1FC4A-J4CN1 FC4A-J8C1 FC4A-J8AT1Analog Input Data 0 to 4095Analog Input Signal Type Analog Input DataVoltage/Current: 0 to 50,000Thermocouple: 0 to 50,000Pt100, Ni100: 0 to 6,000Pt1000, Ni1000: 0 to 60,0000 to 50000 0 to 4000