25: DATA LINK COMMUNICATION« FC4A MICRO SMART USER ’S MANUAL » 25-7Programming WindLDRThe Communication page in the Function Area Settings is used to program for the data link master and slave stations.Since these settings relate to the user program, the user program must be downloaded to the MicroSmart after changingany of these settings.Data Link Master Station1. From the WindLDR menu bar, select Configure > Function Area Settings. The Function Area Setting dialog boxappears.2. Click the Communication tab, and select Data Link Master in the Port 2 pull-down list.3. The Data Link Master Settings dialog box appears. Select a baud rate and the quantity of slave stations. Select a slavestation number from the list on the left and make settings as shown below.4. Click the OK button.Selects the same quantities of transmitand receive data for all slave stations.Baud Rate19200 or 38400 bpsSlave Station Number01 through 31TX: Transmit from masterRX: Receive to masterSelected data quantity0 through 6 wordsTransmit/Receive DataQuantity (Words)Select the quantity of dataregisters for transmit andreceive data per slave station:0 through 6 wordsQuantity of Slave Stations1 through 31Note: When the data link system includes the MICRO3or MICRO3 C, select 19200 bps baud rate, and select 2words of transmit/receive data for MICRO3 or MICRO3 C.