NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM117ENVIROMUX-5D SPECIFICATIONSUser InterfaceLEDs ..............................................................Green – Power (solid when ENVIROMUX is powered ON).............................................................Red – Fault (solid when any sensor is in alert)RJ45 Sensor InputsConnector ......................................................RJ45 connectorVoltage Supply...............................................5VDC and 12VDCMax. Current Supply ......................................50mASignal Type....................................................RS485 for RS485 sensors; 2-wire for contact sensorsMax. Cable Length.........................................1000 FTESD Protection ..............................................IEC 61000-4-2Fuse Protection..............................................Resetable poly fuse – 1.1A (5VDC); 500mA (12VDC) One of each fuse shared by 5ports.Digital InputsConnector ......................................................Detachable terminal block-plug-in, 5 x 2 contactsWire Range....................................................16-26 AWGMax. Input Voltage .........................................25VDCMax. Contact Resistance ...............................300K ohmESD Protection ..............................................IEC 61000-4-2Output RelaysConnector ......................................................Detachable terminal block-plug-in, 2 x 3 contactsWire Range....................................................16-26 AWGOutput Type ...................................................Dry contact, relay isolatedOutput Rating.................................................1A / 30 VDC, 0.5A / 100VACContact Resistance........................................20 milliohmESD Protection ..............................................No, Relay Isolated.Fuse Protection..............................................Non-resetable, 2A Hold, 4A trip, 125VWarning: The digital output contacts are not to be connected directly to AC mains wiring.Alarm PortConnector ......................................................Detachable terminal block-plug-in, 1x2 contactsWire Range....................................................16-26 AWGVoltage Output...............................................12VDC+/-10%Current Output ...............................................180mAESD Protection ..............................................IEC 61000-4-2,Fuse Protection..............................................Resetable poly fuse – 200mA hold, 400mA trip; 16VDC max.USB Device PortsConnector………………………………………USB Type A FemaleVersion………………………………………….USB 2.0 Full Speed compatibleUSB-Serial Port “Console”Connector ......................................................USB Type B FemaleSupported Signals .........................................D+ ,D-Baud Rate......................................................max 115,200 bpsData Format...................................................8 bitsParity..............................................................no parityStop Bits ........................................................1 stop bitsESD Protection ..............................................IEC1000-4-2