NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM49IP DevicesUp to 64 IP addresses can be assigned to be monitored by ENVIROMUX. They will be displayed under the Monitoring->IPDevices item in the left side menu. The ENVIROMUX will periodically ping (test) these addresses to determine whether or notthey are up and running. If the address is not running, an alert will be recorded.For each device the user can configure the∗ IP address,∗ the name,∗ the sensor group the IP device will belong to∗ the ping period (period of time between two consecutive tests),∗ the time-out period (in seconds) in which the address should respond∗ the number of times the ENIROMUX should ping the address before reporting an alert∗ how often, if at all, the reading taken should be added to the data log.If the address fails to respond within the time-out for the selected number of times it will generate an alert. It will be tested againafter the programmed period of time.Just as with other sensors, the method of alert notification and the effect, if any, on output contacts can be configured in responseto IP address connection failures.Figure 53- IP Devices monitoredTo add an IP device to monitor, select “Add New IP Device” from the Monitoring ->IP Devices page.Figure 54- Add new IP DeviceApply a descriptive name for the IP Device to be monitored, and the IP address of the device.