2-18 Operating 15088: K 3/21/01Section ThreeSpecial FunctionThe Special Function feature of the AM2020/AFP1010 allows the operator to generate AM2020/AFP1010status reports or view the AM2020/AFP1010 History File.SSPLFUNCTPress The display will show:PRESS@1=RPTS,2=HIS@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:Enter 1 for a System Configuration report, 2 for an Installed Point report, 3 for a Fire Alarm report, 4 for aTrouble report, 5 for a Disable report, 6 for a Monitor Module On report (including non-fire and securitymonitor modules), or 7 for a Control Module On report.The display will show:Enter 1 to execute the report or 2 to abort a report already in progress.NOTEOnly one report can be conducted at any one time. The reports are not displayed on the DIA.Reports are either displayed on the CRT and/or printed by the printer depending on whether or notprinter reports are redirected to the CRT during programming. An example of a reportprintout is illustrated in Figure 3-1.PRESS@1=SYS,2=POINT,3=ALM,4=TBL,5=DIS,6=MONON,7=CTLON@@@@@@@@@@@@@@@@@@@@@:PRESS 1=REQUEST,2=ABORT@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:SPL FUNCTMenu Option 1Reports