Programming 15088:K 3/21/01 3-53Group 2:Output Modules• These Software Type IDs cannot be programmed for Signal Silence.• These Software Type IDs do not have any control-by-event programming.• If the Software Type ID requires Form-C relay function, the two tabs on the CMX must be broken.Otherwise, the tabs must not be broken.Display LabelALARMS PENDDACT CONNECTGN ALRM FORCGN ALARMGENERAL PENDGN TRBL FORCPAGEPOWER (CONV)GN SUPR FORCTELEPHONETRBLS PENDTROUBLE FORCTROUBLEGN WAT FORCGN WATER FLWType IDAPNDDACTGACGASGPNDGTCPAGEPWRCSSCTELETPNDTRCTRSWFCWFSType of DeviceCMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of an alarm condition, and remain in the ON state until allalarms have been ACKNOWLEDGED.CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C (inrelay mode) that will delay the reporting of AC power loss. Any other troublecondition will be reported immediately. This module is used in conjunction with adigital alarm communicator.CMX Control Module configured as a Form-C relay,an XPR-8 relay, or an XP5-C(in relay mode) to switch power to a Reverse Polarity Trip Device for NFPA 72Remote Station Fire Alarm Systems applications (RPT-680 required).This typecan also be used for general alarm activation.CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-ured as a Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systemsapplications (MBT-1 required).This Type ID can also be used for general alarmactivation.CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of an alarm and/or trouble condition, and remain in theON state until all events have been ACKNOWLEDGED.CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C(in relay mode) activated under any System Trouble condition.CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-ured for remote paging (RPJ-1 required).CMX Control Module configured as a Form-C relay or an XP5-C (in relay mode)used to momentarily interrupt power (during system reset) to conventional 4-wiresmoke detectors powered from a remote main power supply.CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C(in relay mode) activated under any Supervisory condition (includes sprinkler type).CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) config-ured for telephone operation.Note: The CMX and XP5-C will not provide a ring-back signal when a call is placed.CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of a trouble condition, and remain in the ON state until alltroubles have been ACKNOWLEDGED.CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C(in relay mode) that will activate upon receipt of a trouble condition(s) and remainin the ON state until the trouble(s) clear(s).CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of a trouble condition(s) and remain in the ON state untilthe trouble(s) clear(s).CMX Control Module configured as a Form-C relay, an XPR-8 relay, or an XP5-C(in relay mode) activated under any Water Flow condition.CMX Control Module, an XPC-8 circuit, or an XP5-C (in NAC module mode)configured as a Notification Appliance Circuit, activated under any Water Flowalarm condition.