3-12 Programming 15088:K 3/21/01ChangeDetectorVerificationTime?ChangeSignal SilenceInhibit Time?EnableDetectorVerificationTime?Enable SignalSilence InhibitTimeChangeSignal Cut-Out Time?EnableSignal Cut-Out Time?Enter DetectorVerificationTime (5-50 sec)Enter Signal SilenceInhibit Time(1-255 sec)Enter Signal Cut-Out Time(1-2040 sec)Yes YesYes YesYes Yes3 = TDLY(Exit Prog Mode)NoNo NoNoNoNoFigure 1-5 Time Delay Option Flow ChartThe following programming example illustrates enabling all three functions:PRESS@1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM@@@@@ :@3DO@YOU@WANT@TO@CHANGE@THE@DETECTOR@VERIFICATION@TIME?@(Y=YES,N=NO) :@YDO@YOU@WANT@THE@DETECTOR@VERIFICATION@TIME@ENABLED?@(Y=YES,N=NO) :@YENTER@THE@DETECTOR@VERIFICATION@TIME@(5@-@50@IN@1@SECOND@INCREMENTS) :@35DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@SILENCE@INHIBIT@TIME?@(Y=YES,N=NO) :@YDO@YOU@WANT@THE@SIGNAL@SILENCE@INHIBIT@TIME@ENABLED?@(Y=YES,N=NO) :@YENTER@THE@SIGNAL@SILENCE@INHIBIT@TIME@(1@-@255@IN@1@SECOND@INCREMENTS) :@240DO@YOU@WANT@TO@CHANGE@THE@SIGNAL@CUT-OUT@TIME?@(Y=YES,N=NO) :@YDO@YOU@WANT@THE@SIGNAL@CUT-OUT@TIME@ENABLED?@(Y=YES,N=NO) :@YENTER@THE@SIGNAL@CUT-OUT@TIME@(1@-@2040@IN@1@SECOND@INCREMENTS) :@600Section 1.1.3 Time Delays D }X1X3X3=TDLYOption 3 from the Partial System Programming submenu allows the programmer to enable/disable AlarmVerification of detectors, Signal-Silence Inhibit and Signal Cut-out for control modules, as well as setting theappropriate time delays for these functions. For a full description of these functions, see theGlossary of Termsand Abbreviations at the end of this manual.