4-17Security 15088:K 03/21/01MM Security Access MonitorProvide a unique annunciator point for each Security Access Monitor installed.Notification Appliance w/CM ModuleWhen using an optional control module for Notification Appliances intended to indicate a security violation, thecontrol module intended for Tenant A may be programmed with the following Control-By-Event equation:AND(Zab* SDEL(00.00.00 00.15.00 (Zaj*)))and Tenant B may be programmed with the following Control-By-Event equation:AND(Zbb* SDEL(00.00.00 00.15.00 (Zbj*)))resulting in 15 minutes of Notification Appliance activation after a security violation.Program Tenant A using zone numbers Zaa through Zaj as in Figure 1-6. Program Tenant B as in Figure 1-6, but substituteZba through Zbj for Zaa through Zaj respectively. *Zaa through Zaj are each unique installer-specified zone numbers. Zaa is thelowest specified zone number (highest priority) and Zaj is the highest specified zone number (lowest priority).Example:Zaa Zab Zac Zad Zae Zaf Zag Zah Zai ZajZ5 Z12 Z22 Z180 Z188 Z199 Z200 Z210 Z211 Z212Zba Zbb Zbc Zbd Zbe Zbf Zbg Zbh Zbi ZbjZ6 Z7 Z21 Z100 Z102 Z108 Z187 Z191 Z193 Z215ÕÕÕÕÕ ÖÖÖÖÖZone Programming Notes for Figure 1.3-9ÕÖÕÖÕÖÕÖÕÖForward Zones Reverse ZonesZone Boundary greater than or equal to Z22 and less than Z100.The following system requirements are illustrated in Figure 1.3-9. See Table 1.1-1 in the introduction to thissection for monitor and control module options.• One AM2020/AFP1010 Control Panel• Multiple Security Supervisory Circuits Reporting to Central Station as a Single Area• Multiple Protected Premises, each with System Arm/Disarm Capability and Central Station Ringback Signal• The minimum security equipment required is as follows:— Multiple MM Monitor Modules per Protected Area— One Group Interface per Grouped Area— Contact Switch for Each Entry/Exit Door— RKS-S Keyswitch— MM Monitor Modules— ACM-16AT or ACM-32A Remote Annunciator for Each Entry/Exit Door— Security DevicesFigure 1.3-9 Multiple Tenant Security System with Entry/Exit DelayKeyMotion DetectorContact SwitchMM CMMM CMTENANT AAREA 1(PerimeterandInterior)MM CMTENANT BAREA 1(PerimeterandInterior)Contact Switch w/MMMM Security Area MonitorAM2020/AFP1010Central StationRKS-S Remote Keyswitch w/MMPull StationSmoke DetectorGroup Interface *Shaded Area IndicatesSecond TenantACM-16AT or ACM-32A Remote Annunciator* Group Interfacemust be physicallylocated in either theprotected premises orthe Central StationArea7.cdr*SignalingLineCircuit*