ID50 Series Panel - Operating ManualOperator Actions at Panel25 997-264-000-8, Issue 8January 20074.9.5 Outputs - User OptionThe Test Outputs option, accessed from the Test Menu, teststhe panel’s internal sounder and relay circuits and the SignallingLine Circuit (SLC) loop outputs. To perform this test:Test Internal Outputs1 From the Test Menu, press the ‘ 5 ’ button on thenumeric keypad to select the Outputs option.2 Press the ‘ 1 ’ button on the numeric keypad to displaythe Internal Test menu.3 Use the ‘ 2 / 8 ’ buttons to select the internal outputrequired for testing and press the ‘ 5 ’ button to startthe test. The LCD then displays the following:4 Check that the output operates. To stop the test, pressthe ‘ 4 ’ button. Press the ‘ 4 ’ button again to returnto the Test Outputs menu.Test SLC Outputs1 From the Outputs menu, press the ‘ 2 ’ button on thenumeric keypad to display the SLC Output Test menu:2 Use the ‘ 2 / 8 ’ buttons to select the output requiredfor testing and press the ‘ 5 ’ button to start the test.The LCD then displays the following:3 Check that the output operates. To stop the test, pressthe ‘ 4 ’ button. Press the ‘ 4 ’ button again to returnto the Test Outputs menu.[Internal Test] B:01 SDR✓ : Start ↕ : Change Output <:Exit[U0 Outputs] 1:Internal 2:SLC3: Loop Power[Internal Test] B:01 SDROutput test in progress <:Stop[SLC Test] M:nn SDR✓ : Start ↕ : Change Output <:Exit[SLC Test] M:nn SDROutput test in progress <:Stop[U0 Test] 1:LEDs 2:LCD 3:Zones4:Auto High Test 5:Outputs ↕ : More[U0 Outputs] 1:Internal 2:SLC3: Loop Power