ID50 Series Panel - Operating ManualOperator Actions at Panel41 997-264-000-8, Issue 8January 20074.12.4 Input Events - User OptionThe Input Events menu option allows the user to viewactive input events/plant alarms while the normal activeinput events/plant alarms display has been overriddenby a higher priority display (alarms). To view Plant Alarms,from the VIEW Mode menu:1 Using the numeric keypad, press the ‘ 4 ’ button toselect the Input Events display.2 The LCD automatically displays either:a. The first input event, orb. The ‘No Warnings message’, if there are no currentinput events recorded on the system.3 If a number of input events are present, press the‘ 2 / 8 ’ buttons to scroll through the entries:a. Plant Alarm conditionb. Alarm currently displayed.c. Number of alarms.d. Zone Number.e. Device Address.f. Device Type.g. Time alarm was logged.h. Zonal and Device text(if any).Note: Plant alarms for Hold Switch and Abort Switchinputs are entered as AUX events in the Fault list.These input events are not processed by any CBErules.4 Press the ‘ 4 ’ button to return to the View Modemenu.[U0 View] 1:Log 2:Devices 3:Faults4:Input Events 5:Disabled ↕ : MorePLANT 01 / 10 Z21 M12 AUX 14:55< - - - Zone Text - - - > < - - - Device Text - - - >The system has NO warnings present<:ExitPLANT 01 / 10 Z21 M12 AUX 14:55< - - - Zone Text - - - > < - - - Device Text - - - >A B C D E F GHPLANT 02 / 10 Z17 M05 MON 15:05< - - - Zone Text - - - > < - - - Device Text - - - >284