5513.1.8 4-Way Valve Operation Detection Control (Switching Abnormality betweenCooling and Heating) When indoor heat exchanger exceeds 45°C (Cooling operation) or 0°C (Heating and Deice operation) in4 minutes or 3 minutes (Deice operation) after compressor start, compressor will stopped. If above condition occurs 4 times per 30 minutes or 4 times per 40 minutes (non-stop heating deice operation),timer LED blinks "F11" indicated.13.2 Protection Control for Cooling and Soft Dry Operation13.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in thediagram below. This control will begin 1 minute after the compressor starts. Compressor frequency will adjust base on outdoor air temperature.13.2.2 Cooling Overload Control Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operationfrequency). The compressor stop if outdoor pipe temperature exceeds 61°C. If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure riseprotection).13.2.3 Freeze Prevention Control 1 When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stopoperating. Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C. At the same time, indoor fan speed will be higher than during its normal operation. If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normaloperation.13.2.4 Freeze Prevention Control 2 Control start conditionso During Cooling operation and soft dry operation During thermo OFF condition, indoor intake temperature is less than 10°C or Compressor stops for freeze prevention controlo Either one of the conditions above occurs 5 times in 60 minutes. Control contentso Operation stops.o Timer LED blinks and “H99” indicated.