29The XTherm (1005A-2005A) are supplied with an integral Fas-N-Seal vent connector. The installer must use a specificvent starter adapter (supplied by the vent manufacturer).*D-15 Vent Terminal MUST be ordered from Raypak.Model No. M&G Duravent – “Fas-N-Seal”Air Intake Terminal Vent Terminal Vent Pipe Vent Adapter1005A 810003281 810003282 6” Fas-N-Seal6” to 3’ Lengths 8100039741505A 810003369 *D-15 8”(006646)8” Fas-N-Seal6” to 3’ Lengths 8100039802005AModel No. Heat Fab – Saf-T Vent EZ SealAir Intake Terminal Vent Terminal Vent Pipe Vent Adapter1005A 9614TERM 9690TEE 6” Saf-T vent6” to 4’ Lengths 9601RYPK 5601BOI1505A 9814TERM 9890TEE 8” Saf-T vent6” to 4’ Lengths 9801RYPK 5601BOI2005AModel No. Z Flex – “Z Vent”Air Intake Terminal Vent Terminal Vent Pipe Vent Adapter1005A 2SVEE0690 2SVSRTX06 6” Z vent6” to 4’ Lengths 2SVSA061505A 2SVEE0890 2SVSRTX08 8” Z vent6” to 4’ Lengths 2SVSA082005ANOTE: The XTherm heater is supplied with a ventconnector that MAY require a specific vent starter adapterto mate to certified Cat IV stainless steel vent materials(see Table O). This vent starter adapter is supplied bythe vent manufacturer to adapt to the various ventingsystems.NOTE: Installation of a stainless steel vent systemsshall adhere to the stainless steel vent manufacturer’sinstallation instructions supplied with the vent system.Please contact the vent manufacturer with any questions.NOTE: The following stainless steel vent manufacturersare certified for use on these heaters. DO NOT use anymanufacturer of stainless steel vent systems not listedhere. M&G Duravent (FasNSeal Vent), Heat Fab (Saf-T-Vent EZ Seal) and Z Flex (Z-Vent).Table O. Certified Stainless Steel Terminations and Adaptors - Category IV