MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC12 8540780 • 25th June 2012 • Rev.15EnglishInstructions concerning connection cables.Î Wire size range: AWG 12÷30, (solid/stranded) (UL).Î Use 60/75°C copper (Cu) conductor only.Î We recommend the use of separate power supplies for the safety module and forother electrical power equipment (electric motors, inverters, frequency converters)or other sources of disturbance.Î Cables used for connections of longer than 50m must have a cross-section of atleast 1mm2 (AWG16).Connections of each single MOSAIC system unit are listed in the table below:Master M1TERMINAL SIGNAL TYPE DESCRIPTION OPERATION1 24VDC - 24VDC power supply -2 MASTER_ENABLE1 Input Master Enable 1 Input ("type B" according toEN 61131-2 )3 MASTER_ENABLE2 Input Master Enable 2 Input ("type B" according toEN 61131-2 )4 GND - 0VDC power supply -5 OSSD1_A Output Static output 1 PNP active high6 OSSD1_B Output PNP active high7 RESTART_FBK1 Input Feedback/Restart 1 Input according to EN 61131-28 OUT_STATUS1 Output Programmable digital output PNP active high9 OSSD2_A Output Static output 2 PNP active high10 OSSD2_B Output PNP active high11 RESTART_FBK2 Input Feedback/Restart 2 Input according to EN 61131-212 OUT_STATUS2 Output Programmable digital output PNP active high13 OUT_TEST1 Output Short circuit detected output PNP active high14 OUT_TEST2 Output Short circuit detected output PNP active high15 OUT_TEST3 Output Short circuit detected output PNP active high16 OUT_TEST4 Output Short circuit detected output PNP active high17 INPUT1 Input Digital input 1 Input according to EN 61131-218 INPUT2 Input Digital input 2 Input according to EN 61131-219 INPUT3 Input Digital input 3 Input according to EN 61131-220 INPUT4 Input Digital input 4 Input according to EN 61131-221 INPUT5 Input Digital input 5 Input according to EN 61131-222 INPUT6 Input Digital input 6 Input according to EN 61131-223 INPUT7 Input Digital input 7 Input according to EN 61131-224 INPUT8 Input Digital input 8 Input according to EN 61131-2