MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC8540780 • 25th June 2012 • Rev.15 27EnglishÎ T Input_filter = max filtering time from among those set on project inputs (see"INPUTS" section").EnclosureDescription Electronic housing max 24 pole,with locking latch mountingEnclosure material PolyamideEnclosure protection class IP 20Terminal blocks protection class IP 2XFastening Quick coupling to rail according to EN 60715Dimensions (h x l x d) 108 x 22.5 x 114.5M1 modulePFH d (IEC 61508:1998) 6.06E-9Rated voltage 24VDC ± 20%Dissipated power 3W maxUnit enable (No./description) 2 / PNP active high "type B" according to EN 61131-2Digital INPUTS (No./description) 8 / PNP active high according to EN 61131-2INPUT FBK/RESTART (No./description) 2 / EDM control / possible Automaticor Manual operation with RESTART buttonTest OUTPUT (No./description) 4 / to check for short-circuits - overloadsDigital OUTPUTS (No./description) 2 / programmable - PNP active highOSSD (No./description) 2 pairs / solid state safety outputs PNP active high400mA@24VDC maxSLOT for MCM card AvailableConnection to PC USB 2.0 (Hi Speed) - Max cable length: 3mConnection to slave units via MSC 5-way ReeR proprietary busMI8O2 modulePFH d (IEC 61508:1998) 5.72E-9Rated voltage 24VDC ± 20%Dissipated power 3W maxDigital INPUTS (No./description) 8 / PNP active high according to EN 61131-2Test OUTPUT (No./description) 8 / to check for short-circuits - overloadsDigital OUTPUTS (No./description) 2 / programmable - PNP active highOSSD (No./description) 2 pairs / solid state safety outputs:PNP active high – 400mA@24VDC maxConnection to M1 via MSC 5-way ReeR proprietary bus