MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC8540780 • 25th June 2012 • Rev.15 65EnglishFilter (ms): This is used to filter the signals coming from the external contacts. The filtercan be configured to between 3 and 250 ms and eliminates any bouncing on thecontacts. The length of the filter affects the calculation of the unit's total response time.With Contemporaneity: If selected this activates the test to verify concurrent switching ofthe signals coming from the external contacts.Contemporaneity (ms): This is only active if the previous parameter is enabled. It definesthe maximum time (in msecs) between the switching of two different signals from theexternal contacts.Enable Error Out: If selected reports a fault detected by the function block.Item description: This allows a description of the component's function to be entered. Thetext is displayed in the top part of the symbol.MOD-SEL (safety selector)The MOD-SEL function block verifies the statusof the inputs from a mode selector (up to 4inputs): If only one input is 1 (TRUE) thecorresponding output is also 1 (TRUE). In allother cases, and thus when all inputs are 0(FALSE) or more than one input is 1 (TRUE) allthe outputs are 0 (FALSE).ParametersInput type:- Double selector – Allows connection of two-way mode selectors.- Triple selector – Allows connection of three-way mode selectors.- Quadruple selector - Allows connection of four-way mode selectors.Filter (ms): This is used to filter the signals coming from the mode selector. The filter canbe configured to between 3 and 250 ms and eliminates any bouncing on the contacts.The length of the filter affects the calculation of the unit's total response time.Enable Error Out: If selected reports a fault detected by the function block.Item description: This allows a description of the component's function to be entered. Thetext is displayed in the top part of the symbol.PHOTOCELL (safety photocell)The PHOTOCELL function block verifies thestatus of the inputs of an optoelectronic safetyphotocell. If the beam of the photocell isoccupied (photocell output FALSE) the output is0 (FALSE). Otherwise with the beam clear and anoutput of 1 (TRUE) the output is 1 (TRUE).ParametersManual reset: If selected this enables therequest to reset each time safety photocell isactivated. Otherwise, enabling of the outputdirectly follows the input conditions.There are two types of reset: Manual and